Skip to content
← Articles/§ 08·Quality & documentation

Verification of electrical installations

Inspection, testing and documentation per DS/HD 60364-6.

2026-06-16·12 min reading

Verification is not optional — it is a legal requirement that must be carried out by the authorised company before the installation is energised. Here are the sequence, the measurements and the documentation requirements to DS/HD 60364-6.

Introduction

All new and modified electrical installations must be verified before they are energized. Verification consists of two parts: inspection (without power) and testing (with measurements). The order is not accidental – the inspection must always be carried out first. (Source: DS/HD 60364-6, elsikkerhed.dk/krav-til-verifikation)

A. Inspection — de-energized

Inspection is a visual and mechanical check that verifies the installation has been carried out correctly before power is applied. Control points include:

  • 01Protection against electric shock is intact (insulation, enclosure, distances).
  • 02Fire protection and cable selection are correct — e.g. halogen-free cables in escape routes.
  • 03Conductor cross-section and quality correspond to the dimensioning.
  • 04Selection and setting of safety devices (fuses, RCD's) fit the circuit.
  • 05Marking and documentation are in place (course diagrams, panel labels).
  • 06Grounding and potential equalization system is installed correctly (TN-S, TN-C-S, TT or IT as designed).

B. Testing — With Measurements

Testing is performed with instruments and verifies the electrical properties of the installation. The order is set in the standard:

  • 01Continuity in PE conductors and compensation connections.
  • 02Insulation resistance: at least 1 MΩ per circuit (verified stricter requirement acc. to DS/HD 60364-6, table 6.1). (Source: elsikkerhed.dk/krav-til-verifikation)
  • 03Polarity test — phase and neutral are not reversed.
  • 04RCD testing: 0.5× and 5× rated trip current. Example: 30 mA RCD is tested at 15 mA and 150 mA.
  • 05Phase sequence (3-phase systems).
  • 06Voltage drop measurement under expected load – not just calculated, but measured.
  • 07Functional tests of the entire circuit.

Insulation resistance — test voltage and limits

Insulation resistance is measured with an insulation tester (megger) that applies a DC test voltage. Both the test voltage and minimum requirement depend on the circuit's rated voltage (table 6.1 / table 61 in DS/HD 60364-6):

The circuit's nominal voltageTest voltage (DC)Min. insulation resistance
SELV and PELV250 V0,5 MΩ
Up to and including 500 V (incl. FELV)500 V1,0 MΩ
Over 500 V1000 V1,0 MΩ

Measurement is made between the active conductors themselves and between active conductors and earth/PE. Disconnect sensitive electronics and surge protection (SPD), which otherwise can give falsely low results or be damaged by the test voltage. (Source: DS/HD 60364-6, table 6.1 — web-verified.)

Loop impedance and expected fault current

Zs measurement (fault loop impedance) tells whether a fault will trigger protection quickly enough. The instrument temporarily applies a known load and measures the voltage drop. The expected fault current is calculated from Zs:

The rest of the article is locked

Create a free user account to unlock all articles, calculators, templates and range — and get access to quizzes and classes. It takes less than a minute: name, email and a password. No payment card.

Want to try something first? See what you can use without an account — the junior zone, the encyclopedia, the videos and more.