The difference between overload and short circuit, and how the tripping characteristic (B/C/D) of circuit breakers is chosen. Overcurrent covers two phenomena, both of which must be interrupted before the conductor is damaged.
Introduction
Overcurrent covers two different phenomena: overload (an excessive, but not violent, current through an otherwise fault-free circuit) and short circuit (a very large current due to a fault connection with low impedance). Both must be interrupted before the conductor is damaged.
Overload protection
The rated current of the protective device must be coordinated with the conductor's current-carrying capacity so that the conductor does not overheat. The relationship between design current, rated current and current-carrying capacity is laid down in DS/HD 60364-4-43 — the values are looked up there.
Short-circuit protection
In the event of a short circuit, the equipment must trip before the conductor reaches a critical temperature. This sets requirements both for the breaking capacity (the equipment must be able to interrupt the expected short-circuit current) and for the energy (I²t) the conductor is exposed to until disconnection.
Tripping characteristics B, C and D
Miniature circuit breakers have a thermal element (against overload) and a magnetic element (against short circuit). The characteristic describes how quickly the magnetic tripping occurs relative to the rated current:
- 01B — trips at relatively low overcurrent; typically for ordinary domestic and lighting circuits.
- 02C — tolerates a higher short-term inrush current; often used for circuits with motors or many electronic supplies.
- 03D — for loads with heavy inrush surges.
| Characteristic | Magnetic release | Typical use |
|---|---|---|
| B | 3–5 · In | Housing and lighting groups |
| C | 5–10 · In | Motors, many electronic supplies |
| D | 10–20 · In | Transformers, powerful switching surges |
Eksempel: En 16 A C-sikring udløser magnetisk et sted mellem 5 · 16 = 80 A og 10 · 16 = 160 A. Til at eftervise garanteret udkobling ved fejl regnes med den øvre grænse (160 A). (Kilde: DS/EN 60898-1.)
Coordination with the leader
Overbelastningsbeskyttelsen skal koordineres med lederen efter de to uligheder IB ≤ In ≤ Iz og I2 ≤ 1,45 · Iz (se artiklen om kabeltværsnit). Sikringens mærkestrøm må ikke overstige lederens belastningsevne. (Kilde: DS/HD 60364-4-43.)
Members only
The rest of the article is locked
Create a free user account to unlock all articles, calculators, templates and range — and get access to quizzes and classes. It takes less than a minute: name, email and a password. No payment card.
Want to try something first? See what you can use without an account — the junior zone, the encyclopedia, the videos and more.