Skip to content
← Articles/§ 05·Protection & safety

Overcurrent protection

Overload, short circuit and B/C/D characteristics

2026-06-14·10 min reading

The difference between overload and short circuit, and how the tripping characteristic (B/C/D) of circuit breakers is chosen. Overcurrent covers two phenomena, both of which must be interrupted before the conductor is damaged.

Introduction

Overcurrent covers two different phenomena: overload (an excessive, but not violent, current through an otherwise fault-free circuit) and short circuit (a very large current due to a fault connection with low impedance). Both must be interrupted before the conductor is damaged.

Overload protection

The rated current of the protective device must be coordinated with the conductor's current-carrying capacity so that the conductor does not overheat. The relationship between design current, rated current and current-carrying capacity is laid down in DS/HD 60364-4-43 — the values are looked up there.

Short-circuit protection

In the event of a short circuit, the equipment must trip before the conductor reaches a critical temperature. This sets requirements both for the breaking capacity (the equipment must be able to interrupt the expected short-circuit current) and for the energy (I²t) the conductor is exposed to until disconnection.

Tripping characteristics B, C and D

Miniature circuit breakers have a thermal element (against overload) and a magnetic element (against short circuit). The characteristic describes how quickly the magnetic tripping occurs relative to the rated current:

  • 01B — trips at relatively low overcurrent; typically for ordinary domestic and lighting circuits.
  • 02C — tolerates a higher short-term inrush current; often used for circuits with motors or many electronic supplies.
  • 03D — for loads with heavy inrush surges.
CharacteristicMagnetic releaseTypical use
B3–5 · InHousing and lighting groups
C5–10 · InMotors, many electronic supplies
D10–20 · InTransformers, powerful switching surges
B · 3–5·InC · 5–10·InD · 10–20·Inovercurrent (× In)release timethermal(overload)magnetisk udløsning = hurtig kortslutningsbeskyttelse
Fig. Udløsekarakteristik B, C og D: den fælles termiske gren dækker overbelastning, mens den magnetiske udløsning (kortslutning) sker i hvert sit multiplum-bånd — B ved 3–5·In, C ved 5–10·In og D ved 10–20·In (DS/EN 60898-1).

Eksempel: En 16 A C-sikring udløser magnetisk et sted mellem 5 · 16 = 80 A og 10 · 16 = 160 A. Til at eftervise garanteret udkobling ved fejl regnes med den øvre grænse (160 A). (Kilde: DS/EN 60898-1.)

Coordination with the leader

Overbelastningsbeskyttelsen skal koordineres med lederen efter de to uligheder IB ≤ In ≤ Iz og I2 ≤ 1,45 · Iz (se artiklen om kabeltværsnit). Sikringens mærkestrøm må ikke overstige lederens belastningsevne. (Kilde: DS/HD 60364-4-43.)

The rest of the article is locked

Create a free user account to unlock all articles, calculators, templates and range — and get access to quizzes and classes. It takes less than a minute: name, email and a password. No payment card.

Want to try something first? See what you can use without an account — the junior zone, the encyclopedia, the videos and more.