How RCDs (HPFI/RCD), automatic disconnection and equipotential bonding together protect against electric shock. The protection rests on basic protection and fault protection — and the normative limits are always looked up in DS/HD 60364-4-41.
Introduction
Protection against electric shock rests on two pillars: basic protection (live parts cannot be touched during normal operation) and fault protection (you are protected if the insulation fails). Fault protection is typically provided by automatic disconnection of the supply.
Automatic disconnection
The principle is that a dangerous fault must disconnect the supply within a set time. This requires the fault current to be large enough to trip the protective device, and the PE conductor and earth connection to have low enough impedance. The specific disconnection times and impedance limits are laid down in DS/HD 60364-4-41 and depend on the system earthing (TN, TT, IT) — look them up in the applicable standard.
The residual current device (HPFI/RCD)
A residual-current device measures the sum of the currents in the live conductors. If that sum is not (close to) zero, a fault current is leaking to earth and the device trips. A device with a rated residual current of 30 mA provides protection against electric shock in many situations.
- 01The rated residual current is marked on the breaker (e.g. 30 mA, 300 mA).
- 02The type (AC, A, F, B) is chosen according to the nature of the load — for example, electronics with DC components often require at least type A.
- 03The requirement for RCD/RCBO coverage and the choice of type follow the applicable regulation and standard.
Equipotential bonding connections
Protective equipotential bonding connects exposed and extraneous conductive parts so they are kept at (almost) the same potential. This reduces the touch voltage in the event of a fault. Supplementary bonding may be required in special rooms, e.g. bathrooms.
Touch voltage limit UL
Grænsen for, hvor høj en berøringsspænding der må stå på i ubegrænset tid, er UL = 50 V AC (eller 120 V ripplefri DC) i normale, tørre omgivelser. I våde omgivelser og særlige rum er grænsen lavere. Overstiges grænsen ved en fejl, SKAL fejlen kobles ud inden for en fastsat tid — og jo højere spænding, jo kortere tid. (Kilde: DS/HD 60364-4-41.)
Maximum disconnection times
Ved en isolationsfejl må den farlige spænding kun stå på i kort tid. Tabellen gælder ved nominel spænding mod jord U0 = 230 V:
| System | Slutkredse (≤ 32 A) | Fordelings-/hovedkredse |
|---|---|---|
| TN | 0,4 s | 5 s |
| TT | 0,2 s | 1 s |
The TT system requires faster disconnection because fault current flows through earth and is normally handled by an RCD. (Source: DS/HD 60364-4-41, table 41.1.)
Loop impedance determines if it works
Automatic disconnection only works if the fault current becomes large enough to trip the protection within the time. This sets requirements for the fault loop impedance Zs:
Eksempel: En 16 A C-automatsikring udløser magnetisk ved op til Ia = 10 · In = 160 A (top af C-båndet). Kravet bliver Zs ≤ U0/Ia = 230/160 = 1,44 Ω. Måler du en højere Zs på anlægget, når fejlstrømmen ikke op på 160 A hurtigt nok, og den øjeblikkelige udløsning er ikke garanteret inden for tiden — så skal Zs sænkes (kortere/tykkere leder) eller beskyttelsen ændres.
SELV, PELV and FELV
- 01SELV (safety extra-low voltage): maximum 50 V AC, galvanically isolated from earth and from other circuits, supplied from a safety transformer. No earth connection.
- 02PELV: like SELV, but the circuit or device may be earthed — used where earthing is necessary for functional reasons.
- 03FELV (functional extra-low voltage): low voltage for functional reasons, but WITHOUT full isolation. Therefore still requires the same protection as the rest of the system.
SELV and PELV are independent protection methods, because the voltage itself is kept safe. (Source: DS/HD 60364-4-41, section 414.)
Members only
The rest of the article is locked
Create a free user account to unlock all articles, calculators, templates and range — and get access to quizzes and classes. It takes less than a minute: name, email and a password. No payment card.
Want to try something first? See what you can use without an account — the junior zone, the encyclopedia, the videos and more.