Expansion in closed heating systems

Expansion vessel and safety valve

2026-06-14·11 min reading

Why closed systems must accommodate the expansion of the water, what the expansion vessel and safety valve do, and how the expansion volume is calculated.

Introduction

Water expands when it is heated. In a closed system the water cannot escape, so the expansion has to be absorbed somewhere — otherwise the pressure rises uncontrollably.

The expansion vessel

A closed diaphragm expansion vessel absorbs the expansion: as the water expands, the diaphragm is pressed against an air/gas cushion, keeping the pressure rise within the system's limits.

return
Fig. Closed system: the boiler's heat expands the water, the diaphragm tank absorbs the expansion against an air cushion, and the safety valve is the last protection against overpressure.

The expansion factor e is not a fixed constant — it depends on the temperatures and is looked up in a table of the volumetric expansion of water. The nominal vessel size also depends on the pre-charge and system pressure (Boyle's law) and is sized according to the vessel manufacturer's instructions.

The safety valve

  • 01The safety valve is the last line of protection against overpressure and discharges at its set opening pressure.
  • 02It does not replace the expansion vessel — the valve must not operate under normal running conditions.
  • 03The discharge from the valve must be routed safely and visibly in accordance with the applicable rules.

Tank dimensioning step by step

The expansion volume ΔV tells how much water the vessel must take up — but the vessel's nominal size V_n is larger, because the air cushion behind the membrane is compressed according to Boyle's law (p · V = constant), and because there must be a small water reserve so the membrane is never fully emptied. The relationship is the vessel manufacturers' standard formula:

  • 01Pre-charge p_0: set after the system's static height — as a rule of thumb the height in metres from tank to the system's highest point divided by 10 (+ approx. 0.2 bar in practice), but at least approx. 1.0 bar.
  • 02Charge pressure: the system is filled to slightly above the pre-pressure so there is a water reserve on the membrane from the start.
  • 03Max. pressure p_e: chosen below the safety valve opening pressure with margin so the valve does not blow during normal heating.
  • 04Water reserve V_v: a small buffer (manufacturers typically specify a minimum value) so the membrane is not completely empty in cold conditions.

Water's volume expansion e

The expansion volume is calculated as ΔV = V · (e / 100), where e is water's relative volume expansion between the filling and max. operating temperature. e is not a constant, but follows from water's density, which falls with rising temperature. The table is calculated from standard density data with a filling temperature of approx. 10 °C:

Max. operating temperatureRelative expansion e (from ~10 °C)
40 °Capprox. 0.76 %
50 °Capprox. 1.18 %
60 °Capprox. 1.68 %
70 °Capprox. 2.24 %
80 °Capprox. 2.87 %
90 °Capprox. 3.56 %

The values are calculated as (ρ_fill / ρ_max − 1) · 100 based on water density at the two temperatures (e.g. 999.7 kg/m³ at 10 °C and 977.8 kg/m³ at 70 °C gives 2.24 %). If the fill temperature is different, the values change accordingly. (Source: physical substance data for water; VDI 2035.)