Skip to content
← Articles/§ 07·Legislation

DS 452 — Energy classes

The Danish standard for heat loss from technical installations

2026-05-19·8 min reading

Key figures

10

Full title

** DS 452:2013 — Thermal insulation of technical installations (English: *Thermal insulation of technical service and supply systems*)

Current edition

** 3rd edition, 2013 (both the compendium and the lesson material refer to "DS 452-3")

Entry into force

** 1 December 2013 with a transitional period until **31 May 2014**

Official corrigendum

** DS 452:2013/Ret.1:2018, dated 2018-10-02

Previous edition

** DS 452, 2nd edition 1999 (had only 4 classes)

Number of energy classes

** 7 levels in total — class 0 (no insulation) plus classes 1–6

Operating-temperature range

** **−40 °C to +650 °C**

Reference class for distribution lines

** class 4 indoors, class 6 outdoors

ICS codes

** 27.220 (heat recovery, thermal insulation) and 91.120.10 (thermal insulation of buildings)

Publisher

** Dansk Standard, Göteborg Plads 1, DK-2150 Nordhavn

DS 452 establishes 6 energy classes with a max. permitted heat loss per m² of outer surface. We review the classes' values, which installations fall under it (and which do not), and how to read a requirement in practice.

What is DS 452 — and what is it not?

DS 452 is the Danish standard for thermal insulation of technical installations. It establishes how much heat may escape (or enter) through the insulation on a pipe, a duct, a vessel or a fitting — measured as the U-value for the class's surface heat flow. The standard's full title is Thermal insulation of technical service and supply systems, and it is published by Dansk Standard.

It is easy to confuse DS 452 with other standards, so here is the brief delimitation:

StandardScopeConfused with DS 452 because …
DS 452:2013Energy loss from pipes, ducts, tanks, fittings (HVAC + industry)
DS 428Fire insulation of ventilation ducts — resistance to fire spreadBoth concern ducts, but DS 428 is fire, not energy
DS 418Calculation of the U-value of building constructions (walls, roof, floor)Both concern heat loss, but DS 418 is the building envelope, not the installations inside
DS 469Supply and heating systems in general (defines e.g. district-heating units)DS 452 refers to DS 469 for installation units
DS 439Water installations (cold potable water is referred here)DS 452 shows cold potable water, but condensation details are governed by DS 439
DS/EN ISO 12241The calculation method for heat loss from pipes and ductsYou use EN ISO 12241 to show whether the DS 452 requirement is met
DS/EN 1886Classification of the U-value of ventilation unitsDS 452 refers to EN 1886 for the units' T2/T3 classification
DS/EN 253Pre-insulated district-heating pipesDS 452 does not apply to the district-heating supply network

DS 452 explicitly covers all parts of the installation — flat and curved surfaces, ducts, pipe systems, valves, fittings, installation units, units, fans and tanks (quoted from DS 452-3, reproduced in the BAI compendium, p. 6). The key point is that they are operated at a medium temperature between −40 °C and +650 °C — everything from cold-storage rooms to high-temperature steam pipes.

Historical development

DS 452 has existed since the 1980s, but the edition in force today is the 3rd edition from 2013:

  • DS 452, 2nd edition (1999) — had only four insulation classes with permitted U-values of 0.88 / 0.66 / 0.49 / 0.25 W/(m²·K) for flat surfaces. The class was chosen on the basis of "operating parameter I" — a weighted combination of medium temperature, ambient temperature and operating time.
  • DS 452-3 (2013) — entered into force on 1 December 2013 with a transitional period until 31 May 2014. As the BAI compendium writes: "from 31 May 2014 all installations must be insulated according to the new standard." The most important change was the expansion to six classes, a clear division between HVAC and industrial systems, a simple indoor/outdoor boundary at 5 °C, integration of the old DS 1102 on space requirements, as well as new rules for pipe supports (whether they are insulated or not).
  • Corrigendum DS 452:2013/Ret.1:2018 (dated 2018-10-02) — updates, among other things, table 6.2 (reduced insulation), table 6.4 (the requirements table) and annex tables A.1–A.3. The corrigendum also removes references to DS 1135, which has been withdrawn.
  • DS 452-3 new 2020 / subsequent editions — after 2018, Dansk Standard has published consolidated versions with the corrigendum incorporated. The content is technically the same as DS 452:2013 + Ret.1:2018, and the compendium's U-values and requirements table remain the ones in force [UNCERTAIN — the 2020 PDF itself in the source folder is an image scan with no extractable text, so detailed changes from 2018 to 2020 cannot be verified here].

The main line: When a vocational teacher, insulator or consultant says "DS 452", today it means DS 452:2013 with the Ret.1:2018 corrections incorporated. That is the one referred to by both the Isover HVAC Handbook (9th edition, December 2022) and Rockwool.

The 6 classes in detail

The classes in DS 452-3 are U-value requirements for flat surfaces (W/(m²·K)). For round pipes, the compendium provides a corresponding equivalent formula per running metre of pipe, in which the outer diameter D_ep (or p_ep, varying notation) is entered.

ClassU requirement, flat surface W/(m²·K)U requirement, pipe W/(m·K)Typical use
Klasse 0No insulationNo insulationShort connecting lines in the same room as the heat source or tapping point. Connecting ducts in the rooms they serve. Exhaust-air ducts without heat recovery.
Klasse 11.173.3 · D_ep + 0.22Loosest class. Supply-air ducts on systems with mechanical cooling with a design air temperature of 15–23 °C in heated rooms. Short-term operation, small temperature difference.
Klasse 20.882.6 · D_ep + 0.20Connecting lines in rooms other than the heat source (indoors, >5 °C). Cooling pipes for offices and similar (>0 °C). Cold potable water, both with and without electric tracing. Supply-air ducts in air-heating systems >23 °C located indoors. Internal roof drains.
Klasse 30.662.0 · D_ep + 0.18Distribution lines for heating systems operating only during the heating season, ΔT ≤ 45 °C or with outdoor-air compensation. Supply-air ducts <15 °C. Exhaust-air and supply-air ducts on heat-recovery systems outdoors / in unheated rooms.
Klasse 40.491.5 · D_ep + 0.16Reference class for most distribution lines indoors (heating, hot potable water, district heating within the building). Solar-heating pipes. Cooling pipes for server rooms. Supply-air ducts in air-heating systems >23 °C located outdoors. Internal connecting pipes to heat pumps.
Klasse 50.351.1 · D_ep + 0.14Heat exchangers, hot-water tanks and water heaters indoors. Solar-heating tanks indoors. Cold-storage and freezer rooms (medium ≤ 0 °C). Hot connecting pipes to the outdoor unit of an air-to-water/air-to-air heat pump, indoors.
Klasse 60.220.8 · D_ep + 0.12Strictest class. All outdoor installations in the corresponding categories — heating pipes outside the building, hot potable water outdoors, heat exchangers and tanks outdoors, heat-pump pipes outdoors. Year-round operation with high medium temperatures.

Why exactly those numbers? The numbers fall towards higher classes — class 6 (0.22 W/(m²·K)) permits five times less heat loss than class 1 (1.17 W/(m²·K)). The reasoning in the compendium: "It has always been the rising oil prices that formed the basis for these calculations, since the payback time on an insulated pipe had to be in proportion to the operating budget. And with the new classes you can make more targeted calculations." (BAI compendium, p. 6).

For the round pipes it can be seen that the U requirement is a linear function of the outer pipe diameter — this is due to the geometry: one m² of outer surface corresponds to an ever shorter length of the pipe, the larger the diameter. As a rule of thumb: use the flat-surface table when you think in square metres, and the pipe formula when you think in running metres.

The rest of the article is locked

Create a free user account to unlock all articles, calculators, templates and range — and get access to quizzes and classes. It takes less than a minute: name, email and a password. No payment card.

Want to try something first? See what you can use without an account — the junior zone, the encyclopedia, the videos and more.

Sources

  • Dansk Standard. DS 452:2013 — Thermal insulation of technical installations. 3rd edition 2013. Entry into force 1 December 2013, transitional period until 31 May 2014. Publisher: Dansk Standard, Göteborg Plads 1, DK-2150 Nordhavn.
  • Dansk Standard. DS 452:2013/Ret.1:2018 — Corrigendum. 2018-10-02. Updates table 6.2, table 6.4 and annex A.1–A.3; removes the reference to DS 1135.
  • Dansk Standard. DS 452-3, new edition 2020 (consolidated with the 2018 corrigendum) [source folder, but image PDF — technical content corresponds to DS 452:2013 + Ret.1:2018].
  • The Continuing Education Committee for Construction/Civil Engineering & Industry (BAI). Compendium for DS 452-3. Published with support from the Ministry of Education. Vocational teacher Preben Kristensen, AMU Syd Kolding. Verified with energy consultants; quotes from DS 452-3 included with the permission of Dansk Standard.
  • Isover (Saint-Gobain). HVAC Handbook, 9th edition. December 2022. Replaces the 8th edition from December 2021. Classification table pp. 24–25, dimension tables pp. 15–45, space requirements pp. 12–14.
  • Lesson 1 PPTX "DS 452-3 — Classes & Heat Loss" (school material, reproduced in materiale/.extracted/ds452-lektion1.txt).
  • Dansk Standard's public catalogue: ds.dk — search "DS 452".
  • Molio Knowledge System: molio.dk — the construction and consulting industry's collection of technical standards and guidelines.
  • Building Regulations 2018 (BR18), §270 Heating and cooling systems and potable-water systems and §358 Insulation of technical installations — the Danish Transport, Construction and Housing Authority.
  • Project module src/lib/calculations.ts with the implementation of DS452_CLASSES, ds452MaxHeatLoss() and recommendedThicknessForClass().
  • Project module src/lib/hvac-classes.ts with the look-up table from the Isover HVAC Handbook.