Compressive strength for masonry — the f_k formula in Eurocode 6

Stone's and mortar's strength combined in one calculation

2026-06-16·12 min reading

Characteristic compressive strength for masonry f_k is calculated as K · f_b^0,70 · f_m^0,30. Here are the K coefficients, the limits and a worked example.

Introduction

Before you can check a brick wall's load-bearing capacity, you must know the wall's characteristic compressive strength f_k. It combines the stone's normalized strength (f_b) and the mortar's strength (f_m) in a power formula from EN 1996-1-1.

Power formula

K-coefficients (table 3.1)

Stone typeGroupK (general purpose mortar)
Brick / fired clay and sandlime10,55
Brick / fired clay and sandlime20,45
Lightweight concrete10,55
Lightweight concrete20,52
Aerated concrete—0,55

Example

Clay bricks group 1 with f_b = 10 MPa and M10 mortar (f_m = 10 MPa): f_k = 0.55 · 10^0.70 · 10^0.30. Since 10^0.70 · 10^0.30 = 10^1 = 10, f_k = 0.55 · 10 = 5.50 MPa.

Stone and mortar combined for masonry strength^0.7010·^0.3010stone f_b10 MPamortar f_m10 MPacap: f_m ≤ min(20; 2·f_b)K = 0,55combined in the formula10^0,70 · 10^0,30 = 105,5masonry f_k5.5 MPaf_k = K · f_b^0,70 · f_m^0,30
Fig. Kombinationsdiagram: stenens styrke (f_b) og mørtlens styrke (f_m) føres gennem potensformlen f_k = K · f_b^0,70 · f_m^0,30 — søjlerne viser artiklens eksempel (10 MPa + 10 MPa · K = 0,55 → 5,5 MPa), altså at murværket bliver svagere end sine dele

Where does f_b come from? The form factor δ

f_b in the formula is not the stone's declared raw strength. It is the stone's normalised mean compressive strength: the tested mean compressive strength converted to a theoretical stone of 100 × 100 mm. The conversion uses a shape factor δ per DS/EN 772-1, because a low, wide stone measures different compressive strength than a high, narrow one — geometry affects the test.

Example (the method): a unit with a tested mean compressive strength f_st = 30 MPa. If δ is read from table A.1 as e.g. 0.8 for the unit's height/width, f_b = 0.8 · 30 = 24 MPa. The δ value MUST be read from the table for the specific unit — 0.8 is only an illustrative figure here, not a fixed value.

Mortar class and specialist mortars

The formula above applies to general purpose mortar with α = 0.70 and β = 0.30. If thin-layer mortar (glued joints for e.g. aerated concrete) or lightweight mortar is used, both the K value and the exponents change — EN 1996-1-1 cl. 3.6.1.2 has its own expressions for those mortar types (including a different power on f_b and the mortar term dropping out for thin-layer). Always use the expression that matches the actual mortar type.