Nozzle with tab collar on a flat wall

Round spigot in a flat duct wall: the tabbed collar with slot, strain and rivets — plus the hole in the wall.

Exact flat patternLitre-drivenOutside dimensions21 dimensions8 presets
Vvs energi · Smed · Metalsmed …
Plumbing · Insulation
stuts · studs · fligekrave …
stuts · studs · fligekrave · tungekrave · stutskrave · spirostuds · tilslutningsstuds · sadelstuds · afgreningsstuds · kanalstuds · rosette · modflange · tab collar · hulskabelon

How true is the flat pattern?

The surface is developable and the flat pattern is solved in closed form. Cut the part to the drawing and it fits — the whole uncertainty sits in the K-factor, which belongs to the material and the machine, not to the geometry.

Dimensions are entered as: Outside dimensions. The flat pattern itself is always computed on the neutral fibre — at Ø800 in 3 mm sheet the difference between the inside and the outside dimension is 18.8 mm of developed width, and then the seam does not meet.

The vocabulary of bending

The words and formulas the trade uses for a flat pattern. The symbols are the same throughout Discebo: α is the bend angle in degrees, R the inside bend radius, t the sheet thickness and K the K-factor — all in millimetres.

Flat pattern (development)
The part's surface laid out flat as one continuous cutting outline — the way the sheet looks BEFORE it is bent or rolled. Only a developable surface can be unfolded exactly; a doubly curved surface cannot be laid flat without stretching the material.
Flat length
The flat length the part must be cut to so the dimensions come out right once it is bent. It is either the sum of the outside dimensions minus the bend deductions, or the sum of the flat legs plus the bend allowances — both routes must give the same number.L = Σ(udvendige mål) − Σ(BD) = Σ(flade ben) + Σ(BA)
Bend allowance
The length of material that sits in the bend itself, measured along the neutral fibre. The bend allowance is always positive and is added to the flat legs.BA = (π/180) · α · (R + K · t)
Bend deduction
The amount subtracted from the sum of the outside dimensions, because the two outside dimensions between them count the corner twice. Here the bend deduction is taken as POSITIVE and subtracted; DIN 6935 writes the same quantity as the compensation value v with the opposite sign.BD = 2 · OSSB − BA
Outside setback
The distance from the theoretical outside corner point in to where the bend starts. Above 90°, tan(α/2) is clamped to at most 1 per DIN 6935, so the number does not explode towards 180°.OSSB = tan(α/2) · (R + t)
Compensation value v to DIN 6935
The standard's own way of writing the same corner loss: the flat length is a + b + v, where v is negative. Our bend deduction is therefore the same quantity with the opposite sign — never flip one without the other.L = a + b + v ⇒ v = −BD
K-factor
Where the neutral fibre sits in the sheet, given as a fraction of the sheet thickness. DIN 6935 writes the correction factor k, which applies to the neutral line in the form (R + t·k/2); the American CAD convention writes (R + K·t), so K = k/2.k = 0,65 + 0,5 · log₁₀(R/t), k ≤ 1,0 ⇒ K = k/2
Neutral fibre
The layer in the sheet that is neither stretched nor compressed when the part is bent. The flat pattern is always computed on the neutral fibre — which is why it matters whether the drawing's dimensions are inside or outside.
Bend angle
The angle the material is turned through, not the angle between the legs. The bend angle is 180° minus the included angle, so a square corner is 90° and a seam fold is 180°.α = 180° − åbningsvinklen
Inside bend radius
The radius on the inside of the bend. It is set by the tooling and the material, not by the drawing — too small a radius cracks the part in the outer fibre.
Sheet thickness
The thickness of the material. It enters every single bend allowance, so sheet delivered 0.2 mm thicker than ordered shifts the flat length at every bend.
Fold line
The line on the flat pattern where the part is to be bent. It is drawn but never cut through — in a laser file it therefore sits on its own layer.
Test bend
A strip of known raw length, bent in the material and the tooling that production will use. Measure the two outside legs afterwards and the bend deduction and K-factor can be worked back. The machine's own measured bend table beats any table.BD_målt = (A + B) − L₀

DIN 6935 covers only cold bending of flat products in structural steel. Stainless, aluminium, copper, brass and titanium zinc are not included — there the formulas are an extrapolation, and a test bend in the actual material settles it.

The dimensions you type

21 fields. The starting values belong to the figure itself — they live in one place in the code, so the tool, the share link and the smoke test can never disagree about what «default» means.

Dimension in mmIntervalStandardExplanation
Nozzle outside Ødriverstuds_d63–630 mm · step size 1160 mmThe outer dimension — that's what the spiral duct is called by. The commercial sizes are 63 · 80 · 100 · 125 · 160 · 200 · 250 · 315 · 400 · 500 · 630 mm; other dimensions must be confirmed with the supplier.
Goods thicknesst0,5–1,2 mm · step size 0,050,6 mmThe thickness a given duct part REQUIRES is given in DS 447 / EN 1506 — it is an input here.
Free nozzle length above the wallstuds_laengde30–1.000 mm · step size 5150 mmFlat blank dimension from the cutting line up to the pipe's free end. For an oblique nozzle it is the SHORTEST generatrix; the longest becomes 2·R_n·cot θ longer.
Angle between nozzle and duct walltheta30–90 ° · step size 190 °90° = perpendicular to the wall ⇒ round hole. Below 90° the hole becomes an ellipse with major axis D/sin θ.
How the nozzle sits in the wallmontageSet-in — stutsen stikkes ind gennem hullet · Set-on — stutsen sidder på væggen over hulletSet-in — stutsen stikkes ind gennem hulletThe choice changes the hole diameter by 2·t + clearance — it is not a technicality.
Clearance in the holeconditionalspillerum0–3 mm · step size 0,51 mmThe clearance between the outside of the pipe and the edge of the hole, so the spigot can go in without binding.
Collar width (tab length)kravebredde10–40 mm · step size 125 mmFlat blank dimension from the cutting line. The collar costs 2π·ℓ mm of opening at the tab tips — regardless of how many tabs there are.
The tool chooses the number of tabsflige_autoon / offonAims for 30 mm tab width at the root and at least 10 tabs, so the tab can be flattened out.
Number of tabsconditionalflige_antal6–48 stk · step size 116 stkToo few leave gaps that cannot be sealed; too many are unworkable with the tongs.
Gap width between the tabsspalte1–5 mm · step size 0,52 mmThe width of the shear cut itself. It must be at least the machine's cutting width.
Tab shapefligeformLige flige (parallelle snit) · Kileformede flige (smallest ved roden)Lige flige (parallelle snit)—
SecuringfastgoerelsePop rivets (blind rivets) · PladeskruerPop rivets (blind rivets)—
Sealing strip under the collartaetningslisteon / offonThe collar has slits and is not watertight in itself. The strip is included in the length dimension of the parts list.
Mating flange (rosette)rosetteon / offoffFlat ring clamped down over the tabs, so the tips are held flat and the slots are covered.
Rosette rim outside the tab tipsconditionalrosette_rand5–60 mm · step size 115 mm—
Draw the wall section with the holevaegudsniton / offonIf the duct already exists, use the panel as a template — scribe the hole and cut.
AlloyinglegeringHot-dip galvanised DX51D+Z (spiral duct/ventilation) · Stainless 1.4301 / AISI 304 · Stainless 1.4404 / AISI 316L · Aluminium AlMg3 (5754) · Cold-rolled black steel DC01Hot-dip galvanised DX51D+Z (spiral duct/ventilation)—

Advanced fields

4

Hidden by default — they have a sensible default, and most parts do not need them.

Dimension in mmIntervalStandardExplanation
Rivet/screw Øfastgoerelse_d3–6,4 mm · step size 0,24 mm—
Number of fixings (0 = one per tab)fastgoerelser0–48 stk · step size 10 stkA tab without a rivet lifts off the wall. Fewer than one per tab is a deliberate choice.
Wall section margin around the collarconditionalvaeg_margen20–300 mm · step size 560 mm—
Air velocity in the spigotlufthastighed1–15 m/s · step size 0,54 m/sUsed for q = A·v through the opening. The velocity is an INPUT from the project — the limits for noise and pressure loss are set out in DS 447, not here.

Ready-made presets

A preset sets every dimension at once. The name is often the word the part goes by in the workshop — the library's search knows them all.

Connection nozzle Ø160 in rectangular duct

17 tabs at 29.5 mm pitch, 25 mm collar — the gap fans from 2.0 to 11.2 mm

Also known as: tilslutningsstuds · spirostuds · stuts · afgreningsstuds · kanalstuds

Exhaust nozzle for 250 m³/h at 4 m/s

The airflow drives the diameter: A = q/v = 17,361 mm² ⇒ clear bore Ø148.7 mm

Also known as: afkast · udsugningsstuds · luftmængde · m3/h · dimensionering

Ø315 main outlet with rosette

33 tabs, screwed, flat counter-flange 15 mm outside the tab tips

Also known as: hovedafgang · stor studs · rosettestuds · modflange · kravestuds

Oblique spigot 45° in duct side

The hole becomes an ellipse 202 × 284.8 mm, and ε_maks rises by a factor of √2 to 35.5 %

Also known as: skråstuds · 45 grader · skrå afgrening · skævt studs · vinkelstuds

Ø125 hood connection in top plate

Small nozzle, 20 mm collar and Ø3.2 rivets — 13 tabs of 30.1 mm each

Also known as: emhætte · køkkenaftræk · tilslutning · topplade · aftræksstuds

Ø200 with wedge-shaped tabs

The wedge halves the surface shortfall of the root arc — the gap at the tip is the same

Also known as: kileflig · kilekrave · trapezflig · fligekrave · tungekrave

Ø160 stainless in commercial kitchen extract

1.4301 in 0.8 mm, set-on so no material stands in the grease flow

Also known as: storkøkken · rustfri studs · fedtaftræk · emfang · 1.4301

Ø500 main nozzle in air handling unit duct

48 tabs — the blank is 1,568 mm wide, so the pipe is bought as spiral duct

Also known as: hovedstuds · aggregat · stor spiro · hovedkanal · ventilationsaggregat

Reservation

Read them before the part is cut. They are here because they cannot be calculated away — not as legal text, but as craft.

  • The figure does not size the duct. Which material thickness, which stiffening and which leakage class a given duct side requires is given in DS 447 and EN 1505/EN 1507 — that is an input here.
  • Tightness is not geometry. A tabbed collar by definition has open gaps at the tab tips, and the leakage class in accordance with EN 12237 (round ducts) must be achieved with a sealing strip, mastic or tape, and documented by testing.
  • The fixing's LOAD CAPACITY has not been calculated. The rivet and screw spacings (edge distance ≥ 2·Ø, pitch ≤ 8·Ø) are guidance-only workshop practice from the blind-rivet suppliers' installation instructions — not a standard. Only the hole Ø is standard-backed (DIN 7337 / ISO 15977).
  • Fire dampers and fire-protected penetrations are NOT covered. A damper in a fire-compartment separation is certified equipment to EN 15650 and must not be installed according to this figure.
  • The commercial range 63–630 mm is a GUIDANCE-ONLY stock list. The nominal diameters for round sheet-metal ducts are given in EN 1506; what is in stock is with the supplier — the tool does not invent it.
  • The air velocity is an input. The limits for noise, pressure loss and balancing belong to the ventilation project (DS 447) and are not in the figure.
  • The nozzle's free end is supplied without an edge allowance. A bead or flange on a round rim is stretching (ε = b/R_n), not bending — the press brake's bend allowance does not apply there, and above 5% the edge cannot be formed in one piece.
  • Insulation and vapour barrier around the nozzle are not in the figure. A cold duct must have a continuous vapour barrier at the penetration, and that belongs to the insulation trade.