Skip to content

Rectangular duct, straight section

Straight rectangular duct section with longitudinal seam — Pittsburgh, S-lock, snap-lock, welded or riveted, built from 1, 2 or 4 blanks.

Exact flat patternLitre-drivenInside dimensions20 dimensions12 presets
Vvs energi · Smed · Metalsmed …
Plumbing · Insulation
firkantkanal · rektangulær kanal …
firkantkanal · rektangulær kanal · kanalstykke · ventilationskanal · blikkanal · lige kanal · kanalsektion · pittsburghfals · pittsburgh-lås · snap-lock · hjørnefals · s-fals · drivkile · kanalblik · pasbid

How true is the flat pattern?

The surface is developable and the flat pattern is solved in closed form. Cut the part to the drawing and it fits — the whole uncertainty sits in the K-factor, which belongs to the material and the machine, not to the geometry.

Dimensions are entered as: Inside dimensions. The flat pattern itself is always computed on the neutral fibre — at Ø800 in 3 mm sheet the difference between the inside and the outside dimension is 18.8 mm of developed width, and then the seam does not meet.

The vocabulary of bending

The words and formulas the trade uses for a flat pattern. The symbols are the same throughout Discebo: α is the bend angle in degrees, R the inside bend radius, t the sheet thickness and K the K-factor — all in millimetres.

Flat pattern (development)
The part's surface laid out flat as one continuous cutting outline — the way the sheet looks BEFORE it is bent or rolled. Only a developable surface can be unfolded exactly; a doubly curved surface cannot be laid flat without stretching the material.
Flat length
The flat length the part must be cut to so the dimensions come out right once it is bent. It is either the sum of the outside dimensions minus the bend deductions, or the sum of the flat legs plus the bend allowances — both routes must give the same number.L = Σ(udvendige mål) − Σ(BD) = Σ(flade ben) + Σ(BA)
Bend allowance
The length of material that sits in the bend itself, measured along the neutral fibre. The bend allowance is always positive and is added to the flat legs.BA = (π/180) · α · (R + K · t)
Bend deduction
The amount subtracted from the sum of the outside dimensions, because the two outside dimensions between them count the corner twice. Here the bend deduction is taken as POSITIVE and subtracted; DIN 6935 writes the same quantity as the compensation value v with the opposite sign.BD = 2 · OSSB − BA
Outside setback
The distance from the theoretical outside corner point in to where the bend starts. Above 90°, tan(α/2) is clamped to at most 1 per DIN 6935, so the number does not explode towards 180°.OSSB = tan(α/2) · (R + t)
Compensation value v to DIN 6935
The standard's own way of writing the same corner loss: the flat length is a + b + v, where v is negative. Our bend deduction is therefore the same quantity with the opposite sign — never flip one without the other.L = a + b + v ⇒ v = −BD
K-factor
Where the neutral fibre sits in the sheet, given as a fraction of the sheet thickness. DIN 6935 writes the correction factor k, which applies to the neutral line in the form (R + t·k/2); the American CAD convention writes (R + K·t), so K = k/2.k = 0,65 + 0,5 · log₁₀(R/t), k ≤ 1,0 ⇒ K = k/2
Neutral fibre
The layer in the sheet that is neither stretched nor compressed when the part is bent. The flat pattern is always computed on the neutral fibre — which is why it matters whether the drawing's dimensions are inside or outside.
Bend angle
The angle the material is turned through, not the angle between the legs. The bend angle is 180° minus the included angle, so a square corner is 90° and a seam fold is 180°.α = 180° − åbningsvinklen
Inside bend radius
The radius on the inside of the bend. It is set by the tooling and the material, not by the drawing — too small a radius cracks the part in the outer fibre.
Sheet thickness
The thickness of the material. It enters every single bend allowance, so sheet delivered 0.2 mm thicker than ordered shifts the flat length at every bend.
Fold line
The line on the flat pattern where the part is to be bent. It is drawn but never cut through — in a laser file it therefore sits on its own layer.
Test bend
A strip of known raw length, bent in the material and the tooling that production will use. Measure the two outside legs afterwards and the bend deduction and K-factor can be worked back. The machine's own measured bend table beats any table.BD_målt = (A + B) − L₀

DIN 6935 covers only cold bending of flat products in structural steel. Stainless, aluminium, copper, brass and titanium zinc are not included — there the formulas are an extrapolation, and a test bend in the actual material settles it.

The dimensions you type

20 fields. The starting values belong to the figure itself — they live in one place in the code, so the tool, the share link and the smoke test can never disagree about what «default» means.

Dimension in mmIntervalStandardExplanation
The cladding is built fromantal_emner1 emne — L-rullet, ét søm · 2 emner — to L-stykker, to sømme · 4 emner — fire plane vægge1 emne — L-rullet, ét sømOne piece has three bent corners and one seam; four pieces have no bends and four seams. The choice determines both how wide the blank becomes and how many seam allowances must be paid for.
Longitudinal seamsoemtypePittsburgh lock (pocket + male) · S-fals med drivkile (skinne) · Hjørnefals — snap-lock · Svejst hjørne (stumpsøm) · Nittet vinkel i hjørnetPittsburgh lock (pocket + male)The Pittsburgh lock is asymmetric: a 25.40 mm pocket and a 7.94 mm male edge. The allowances for the other types are the figure's suggestion and must be checked against the seaming machine's roll set.
End finishendeforbindelseEnkel flange (bukket ud 90°) · Vinkelramme (påsat profil) · TDC/TDF-fals (integreret) · Muffe (indstukket samling)Enkel flange (bukket ud 90°)Only the angle frame costs no sheet — it is an applied profile. The socket is ASYMMETRIC: the allowance is only on the outlet end.
Clear dimension A (width)driverbredde_a100–2.000 mm · step size 5400 mmINSIDE dimension. It is the clear dimension that carries the air; the blank is calculated on clear dimension + 2·t.
Clear dimension B (height)driverhoejde_b100–1.250 mm · step size 5400 mmINSIDE dimension. The height is often the one locked by the clearance above a suspended ceiling.
Piece lengthlaengde100–3.000 mm · step size 101.200 mmThe net length between the end terminations. The end allowance is added on top by the edge-allowance layer, so the blank becomes longer than the figure stated here.
End finish widthconditionalende_bredde0–60 mm · step size 120 mmThe flange's external dimension, the TDC seam's height or the socket's insertion length. The dimension is given on the flange system's data sheet — the tool does not invent it.
Root gap in the corner seamconditionalsvejse_rodaabning0–4 mm · step size 0,10,5 mmThe root gap is SUBTRACTED FROM the blank (flat = −g). If forgotten, the cross-section will be g mm too large in circumference.
Seam allowance, part A (pocket/strap)conditionalsoem_tillaeg_a0–60 mm · step size 0,010 mm0 = use the figure's suggestion for the selected seam type. The Pittsburgh pocket is 25.40 mm.
Seam allowance, part B (male)conditionalsoem_tillaeg_b0–60 mm · step size 0,010 mm0 = use the figure's suggestion. The Pittsburgh lock is 7.94 mm — NEVER set the same figure as part A, or the circumference will be 17.46 mm too large.
Stiffening grooves per piecestivrille_antal0–20 stk. · step size 10 stk.Rolled beads across the duct. They are rolled on a beading machine and are not bends.
Goods thicknessgodstykkelse0,5–2 mm · step size 0,050,7 mmDuct sheet. The thickness a given duct side REQUIRES is given in DS 447 / EN 1505 — it is an input here.
MaterialmaterialevalgSom værkstedets (fra opsætningen) · Varmforzinket stålplade (DX51D+Z) · Stainless steel · AluminumSom værkstedets (fra opsætningen)—
System typeanlaegstypeKomfortventilation · Proces- og punktudsugningKomfortventilationDetermines how the velocity is read. In comfort systems a high velocity means noise; in process extraction it is a prerequisite for carrying the material along.
Air velocitylufthastighed0,5–20 m/s · step size 0,14 m/sOnly used to convert the cross-section to an air volume: q = A · v · 3600.
Coil/strip widthcoilbredde800–2.000 mm · step size 501.250 mmDuct sheet is bought in coil. The blank must fit within the width in at least one of its two directions — otherwise the shell must be divided into several pieces.

Advanced fields

4

Hidden by default — they have a sensible default, and most parts do not need them.

Dimension in mmIntervalStandardExplanation
Groove depth hconditionalstivrille_h0,5–8 mm · step size 0,12 mmThe extra length goes as h², so the depth counts four times as much as the width.
Groove width wconditionalstivrille_w3–40 mm · step size 110 mmΔ = 8·h²/(3·w) per groove. Three grooves of h = 2, w = 8 mm eat up 4.0 mm.
Add the extra length of the grooves to the blankconditionalstivrille_kompenseron / offoff8·h²/(3·w) is the geometric UPPER limit. A rolled bead in thin sheet stretches the material more than it draws it in from the edges — measure on a sample before compensating fully.
Inside bend radiusbukkeradius0–10 mm · step size 0,10 mm0 = R is set equal to the material thickness, as air bending itself produces. The machine's own bend table takes precedence over any formula.

Ready-made presets

A preset sets every dimension at once. The name is often the word the part goes by in the workshop — the library's search knows them all.

Branch duct 900 m³/h (250 × 250)

250 × 250 clear opening at 4.0 m/s = 900 m³/h — Pittsburgh, one part, 0.7 mm

Also known as: grenkanal · stikkanal · afgreningskanal · lille kanal · 250x250

Distribution duct 1,800 m³/h (500 × 250)

500 × 250 clear opening at 4.0 m/s = 1,800 m³/h — aspect ratio 2 : 1, one part

Also known as: fordelingskanal · hovedgren · 500x250 · flad kanal · loftkanal

Main duct 7,200 m³/h (1000 × 500)

1000 × 500 clear opening at 4.0 m/s = 7,200 m³/h — two L-halves, TDC seam, four stiffening beads

Also known as: hovedkanal · stamkanal · 1000x500 · stor kanal · TDC

Large duct 1600 × 1000 — four flat walls

Four walls, four seams, no bends: widest blank approx. 1,636 mm against approx. 5,236 mm for a single piece

Also known as: storkanal · hovedkanal · fire emner · 1600x1000 · kanalkasse

Process extraction in stainless, welded

Welded corner with 0.5 mm root gap — tight duct without seam gaps, 10 m/s conveying velocity

Also known as: procesudsugning · point extraction · spånsug · rustfri kanal · svejst kanal

Kitchen extraction — tight and easy to clean

Welded corner, stainless 1.0 mm, flange 30 mm: no gaps that can collect grease

Also known as: køkkenudsugning · emfangskanal · fedtkanal · storkøkken · udsugningskanal

Duct with S-seam and drive cleat

Both edges bent out 15 mm; the rail is slid over and is not part of the blank

Also known as: s-fals · drivkile · drive slip · skinnesamling · kanalskinne

Snap-lock corner seam (roll-formed)

Pocket 12.7 mm and male 6.35 mm — asymmetric like Pittsburgh, just smaller

Also known as: snap-lock · snaplås · button punch · hjørnefals · klikfals

Duct section with inserted sleeve

Only the outlet end gets the extra 30 mm — the inlet end is clean, otherwise the piece becomes 30 mm too long

Also known as: muffe · muffesamling · indstik · slip joint · teleskopsamling

Flat duct for suspended ceiling (1000 × 200)

Aspect ratio 5 : 1 costs 611 mm more circumference per metre than a square duct with the same cross-section

Also known as: flad kanal · nedhængt loft · lav kanal · 1000x200 · loftkanal

Aluminium duct (light, corrosion-resistant)

Aluminium 1.0 mm with riveted corner angle — 2.70 against steel's 7.85 kg/dm³

Also known as: aluminiumkanal · alukanal · letkanal · korrosionsfast kanal · nittet kanal

Make-up piece — short intermediate piece

300 mm long adapter piece: the end allowances take up 37.3 mm of the blank's 337.3 mm

Also known as: pasbid · mellemstykke · tilpasningsstykke · kort stykke · pasrør

Reservation

Read them before the part is cut. They are here because they cannot be calculated away — not as legal text, but as craft.

  • A × B are INTERNAL clear dimensions. The blank is calculated on the outer dimension A + 2·t, and it is the clear dimension that determines the air volume — not the dimension the duct is hung or insulated by.
  • The figure does not size the duct. Which material thickness, which stiffening and which leakage class a given duct side requires is given in DS 447 and EN 1505/EN 1507 — that is an input here.
  • Tightness, pressure loss and sound are NOT covered. The leakage class in accordance with EN 12237/EN 1507 must be documented by testing on the finished installation, not by a development pattern.
  • Fire dampers, fire-insulated ducts and smoke ventilation ducts are not covered. They are certified components to EN 15650 and EN 12101 respectively and must not be manufactured from a development.
  • Only the Pittsburgh lock's 25.40/7.94 mm are traceable figures. Seam allowances for S-lock, snap-lock and TDC/TDF depend on the seaming machine's roll set and are given in the machine's data sheet — the tool does not invent them.
  • Hangers, expansion and support are not covered. The spacing between hangers depends on duct size, material thickness and load, and belongs to the hanger plan.
  • Springback is not compensated for. The development is calculated on the DESIRED 90° angle; how much must be over-bent depends on material, thickness and V-opening and belongs on the machine.
  • The stiffening beads' extra length 8·h²/(3·w) is the geometric UPPER limit. A rolled bead in thin sheet stretches the material locally instead of drawing it in from the edges — check the compensation on a sample.

Onward from here